86-0536-3083857
The HL-1000 water cooling system equipment for sale
The HL-1000 water cooling system equipment for sale
Usage
HL series closed water cooling tower is designed and manufactured by Weifang Jinhuaxin Electric Furnace Manufacturing Co., Ltd., is high in efficiency, low in energy consumption, tighten in structure. Wide Used in MF Induction Furnace, power Supply, furnace Heating equipment cooling and other industrial equipment.
The HL-1000 water cooling system equipment for sale
Advantage
1)Fully enclosed circulating cooling, eliminate the pipeline jams caused by debris.
2)Use soft water circulating cooling; no overheat damage of power supply, silicon control, capacitor, IGBT module, induction coil caused by incrustation.
3)No need of water pool and cooling tower, occupies small area, and moves easily.
4)High cooling efficiency and low operate cost.
5)Low water consumption, meet requirement of environment protection.
The HL-1000 water cooling system equipment for sale
Working Principle
HL series of closed cooling tower equipment is composed by host part, circulating pump system, and electrical control system. The fluid coolers host part is composed by the galvanized steel sprayhousing, condenser/cooler, fan, spray system, S-type water separator, sinks and other parts. Equivalent to a combination of heat exchangers, open cooling tower circulating pump system, pool as a whole, compact structure, beautiful appearance and generous.
The working principle is that the spray cooler indirectly heat exchange,energy efficient. During work process, requires cooling medium conveyed by the circulating pump to be cooled circulating within the condenser brass, through the spray pump spray water evenly sprayed into the heat exchange in the condensersurface, while a portion of the water was evaporated away the heat, the hot and humid air from the tower and then by the fan body.
Closed cooling tower run in two modes: air-cooled; air-cooled and spray. Two modes according automatically switches to the conditions required by the electronic control system to achieve energy saving.
Parameters
Model | HL-600 | |
Cooling Ability(Kcal/h) | 180600 | |
Work Pressure(Mpa.) | 0.25 | |
Work Flow(m3/h) | 22 | |
Inlet Outlet Tube Dia.(mm) | DN80 | |
Rated Power(KW) | Fan | 2.2 |
Water Pump | 4.0 | |
Main Machine | Dimension (mm) | 2800*1300*2000 |
Weight (kg) | 1380 |